Rappel de véhicule

Numéro de rappel de Transports Canada - 2017627 - KEYSTONE

Dernière mise à jour

Résumé

Produit
Autocaravane rappelé par KEYSTONE
Problème
Véhicules - Accessoires
Ce qu’il faut faire

Veuillez consulter la section des mesures correctives ci-dessous

Produits visés

2003 | CROSSROADS | CROSSROADS, 2003 | DUTCHMEN | ADIRONDACK, 2003 | DUTCHMEN | AERO, 2003 | DUTCHMEN | AEROLITE, 2003 | DUTCHMEN | AEROSTAR, 2003 | DUTCHMEN | BRECKENRIDGE, 2003 | DUTCHMEN | COLORADO, 2003 | DUTCHMEN | DUTCHMEN, 2003 | DUTCHMEN | FOUR WINDS, 2003 | DUTCHMEN | KODIAK, 2003 | KEYSTONE | BOBCAT, 2003 | KEYSTONE | CABANA, 2003 | KEYSTONE | CHALLENGER, 2003 | KEYSTONE | COUGAR, 2003 | KEYSTONE | EVEREST, 2003 | KEYSTONE | HORNET, 2003 | KEYSTONE | HORNET HIDEOUT, 2003 | KEYSTONE | LAREDO, 2003 | KEYSTONE | MONTANA, 2003 | KEYSTONE | MONTANA BIG SKY, 2003 | KEYSTONE | MONTANA MOUNTAINEER, 2003 | KEYSTONE | OUTBACK, 2003 | KEYSTONE | SPRINGDALE, 2003 | KEYSTONE | SPRINTER, 2003 | KEYSTONE | TAIL-GATOR, 2004 | CROSSROADS | CROSSROADS, 2004 | CROSSROADS | CRUISER, 2004 | CROSSROADS | PARADISE POINT, 2004 | CROSSROADS | SILVERADO, 2004 | DUTCHMEN | ADIRONDACK, 2004 | DUTCHMEN | AERO, 2004 | DUTCHMEN | AEROLITE, 2004 | DUTCHMEN | BRECKENRIDGE, 2004 | DUTCHMEN | COLORADO, 2004 | DUTCHMEN | DUTCHMEN, 2004 | DUTCHMEN | FOUR WINDS, 2004 | DUTCHMEN | KODIAK, 2004 | DUTCHMEN | SKAMPER, 2004 | DUTCHMEN | TAB, 2004 | KEYSTONE | CABANA, 2004 | KEYSTONE | CHALLENGER, 2004 | KEYSTONE | COUGAR, 2004 | KEYSTONE | EVEREST, 2004 | KEYSTONE | HORNET, 2004 | KEYSTONE | HORNET HIDEOUT, 2004 | KEYSTONE | LAREDO, 2004 | KEYSTONE | MONTANA, 2004 | KEYSTONE | MONTANA BIG SKY, 2004 | KEYSTONE | MONTANA MOUNTAINEER, 2004 | KEYSTONE | OUTBACK, 2004 | KEYSTONE | RAPTOR, 2004 | KEYSTONE | SPRINGDALE, 2004 | KEYSTONE | SPRINTER, 2004 | KEYSTONE | TAIL-GATOR, 2004 | KEYSTONE | ZEPPELIN, 2005 | CROSSROADS | CROSS TERRAIN, 2005 | CROSSROADS | CRUISER, 2005 | CROSSROADS | PARADISE POINT, 2005 | CROSSROADS | SILVERADO, 2005 | CROSSROADS | ZINGER, 2005 | DUTCHMEN | ADIRONDACK, 2005 | DUTCHMEN | AEROLITE, 2005 | DUTCHMEN | BAYRIDGE, 2005 | DUTCHMEN | BRECKENRIDGE, 2005 | DUTCHMEN | COLORADO, 2005 | DUTCHMEN | DENALI, 2005 | DUTCHMEN | DUTCHMEN, 2005 | DUTCHMEN | EXPRESS, 2005 | DUTCHMEN | FOUR WINDS, 2005 | DUTCHMEN | GRAND JUNCITON, 2005 | DUTCHMEN | KODIAK, 2005 | DUTCHMEN | NORTHSHORE, 2005 | DUTCHMEN | SKAMPER, 2005 | DUTCHMEN | T@B, 2005 | DUTCHMEN | TUNDRA, 2005 | DUTCHMEN | VICTORY LANE, 2005 | DUTCHMEN | WILD THING, 2005 | DUTCHMEN | WINNERS CIRCLE, 2005 | KEYSTONE | CHALLENGER, 2005 | KEYSTONE | COUGAR, 2005 | KEYSTONE | EVEREST, 2005 | KEYSTONE | HORNET, 2005 | KEYSTONE | HORNET HIDEOUT, 2005 | KEYSTONE | LAREDO, 2005 | KEYSTONE | MONTANA, 2005 | KEYSTONE | MONTANA BIG SKY, 2005 | KEYSTONE | MONTANA MOUNTAINEER, 2005 | KEYSTONE | OUTBACK, 2005 | KEYSTONE | OUTBACK SYDNEY, 2005 | KEYSTONE | RAPTOR, 2005 | KEYSTONE | SPRINGDALE, 2005 | KEYSTONE | SPRINGDALE CLEARWATER, 2005 | KEYSTONE | SPRINTER, 2005 | KEYSTONE | TAIL-GATOR, 2005 | KEYSTONE | ZEPPELIN, 2006 | CROSSROADS | BELAIR, 2006 | CROSSROADS | CROSS TERRAIN, 2006 | CROSSROADS | CROSSFIRE, 2006 | CROSSROADS | CROSSFORCE, 2006 | CROSSROADS | CRUISER, 2006 | CROSSROADS | PARADISE POINT, 2006 | CROSSROADS | SUNSET TRAIL, 2006 | CROSSROADS | ZINGER, 2006 | DUTCHMEN | ADIRONDACK, 2006 | DUTCHMEN | AEROLITE, 2006 | DUTCHMEN | BAYRIDGE, 2006 | DUTCHMEN | BRECKENRIDGE, 2006 | DUTCHMEN | COLORADO, 2006 | DUTCHMEN | DENALI, 2006 | DUTCHMEN | DUTCHMEN, 2006 | DUTCHMEN | EXPRESS, 2006 | DUTCHMEN | FOUR WINDS, 2006 | DUTCHMEN | FREEDOM SPIRIT, 2006 | DUTCHMEN | GRAND JUNCITON, 2006 | DUTCHMEN | KODIAK, 2006 | DUTCHMEN | KOMFORT, 2006 | DUTCHMEN | MONTE VISTA, 2006 | DUTCHMEN | NORTHSHORE, 2006 | DUTCHMEN | RAINER, 2006 | DUTCHMEN | SKAMPER, 2006 | DUTCHMEN | T@B, 2006 | DUTCHMEN | TUNDRA, 2006 | DUTCHMEN | VICTORY LANE, 2006 | DUTCHMEN | WILD THING, 2006 | DUTCHMEN | WINNERS CIRCLE, 2006 | KEYSTONE | CAMBRIDGE, 2006 | KEYSTONE | CHALLENGER, 2006 | KEYSTONE | COUGAR, 2006 | KEYSTONE | EVEREST, 2006 | KEYSTONE | HOBBI, 2006 | KEYSTONE | HORNET, 2006 | KEYSTONE | HORNET HIDEOUT, 2006 | KEYSTONE | HORNET RETREAT, 2006 | KEYSTONE | LAREDO, 2006 | KEYSTONE | MONTANA, 2006 | KEYSTONE | MONTANA BIG SKY, 2006 | KEYSTONE | MONTANA MOUNTAINEER, 2006 | KEYSTONE | NRG, 2006 | KEYSTONE | OUTBACK, 2006 | KEYSTONE | OUTBACK SYDNEY, 2006 | KEYSTONE | RAPTOR, 2006 | KEYSTONE | SPRINGDALE, 2006 | KEYSTONE | SPRINGDALE CLEARWATER, 2006 | KEYSTONE | SPRINTER, 2006 | KEYSTONE | TAIL-GATOR, 2006 | KEYSTONE | VR1, 2006 | KEYSTONE | ZEPPELIN, 2007 | CROSSROADS | CROSS TERRAIN, 2007 | CROSSROADS | CROSSFIRE, 2007 | CROSSROADS | CROSSFORCE, 2007 | CROSSROADS | CRUISER, 2007 | CROSSROADS | PARADISE POINT, 2007 | CROSSROADS | SUNSET TRAIL, 2007 | CROSSROADS | ZINGER, 2007 | DUTCHMEN | ADIRONDACK, 2007 | DUTCHMEN | AEROLITE, 2007 | DUTCHMEN | BAYRIDGE, 2007 | DUTCHMEN | BRECKENRIDGE, 2007 | DUTCHMEN | COLORADO, 2007 | DUTCHMEN | DENALI, 2007 | DUTCHMEN | DUTCHMEN, 2007 | DUTCHMEN | ECO, 2007 | DUTCHMEN | EXPRESS, 2007 | DUTCHMEN | FOUR WINDS, 2007 | DUTCHMEN | FREEDOM SPIRIT, 2007 | DUTCHMEN | GRAND JUNCITON, 2007 | DUTCHMEN | KODIAK, 2007 | DUTCHMEN | KOMFORT, 2007 | DUTCHMEN | MONTE VISTA, 2007 | DUTCHMEN | N'TENSE, 2007 | DUTCHMEN | NORTHSHORE, 2007 | DUTCHMEN | RAINER, 2007 | DUTCHMEN | T@B, 2007 | DUTCHMEN | TUNDRA, 2007 | DUTCHMEN | VICTORY LANE, 2007 | DUTCHMEN | WILD THING, 2007 | DUTCHMEN | WINNERS CIRCLE, 2007 | DUTCHMEN | ZOOM, 2007 | KEYSTONE | CHALLENGER, 2007 | KEYSTONE | COUGAR, 2007 | KEYSTONE | EVEREST, 2007 | KEYSTONE | FREEDOMLITE, 2007 | KEYSTONE | FUZION, 2007 | KEYSTONE | HIDEOUT, 2007 | KEYSTONE | HOBBI, 2007 | KEYSTONE | HORNET, 2007 | KEYSTONE | HORNET RETREAT, 2007 | KEYSTONE | LAREDO, 2007 | KEYSTONE | MONTANA, 2007 | KEYSTONE | MONTANA BIG SKY, 2007 | KEYSTONE | MONTANA MOUNTAINEER, 2007 | KEYSTONE | NRG, 2007 | KEYSTONE | OUTBACK, 2007 | KEYSTONE | OUTBACK SYDNEY, 2007 | KEYSTONE | PASSPORT, 2007 | KEYSTONE | RAPTOR, 2007 | KEYSTONE | SPRINGDALE, 2007 | KEYSTONE | SPRINGDALE CLEARWATER, 2007 | KEYSTONE | SPRINGDALE SUMMERLAND, 2007 | KEYSTONE | SPRINTER, 2007 | KEYSTONE | VR1, 2007 | KEYSTONE | ZEPPELIN, 2008 | CROSSROADS | CROSS TERRAIN, 2008 | CROSSROADS | CROSSFIRE, 2008 | CROSSROADS | CROSSFORCE, 2008 | CROSSROADS | CRUISER, 2008 | CROSSROADS | HAMPTON, 2008 | CROSSROADS | KINGSTON, 2008 | CROSSROADS | PARADISE POINT, 2008 | CROSSROADS | SEVILLE, 2008 | CROSSROADS | SUNSET TRAIL, 2008 | CROSSROADS | ZINGER, 2008 | DUTCHMEN | ADIRONDACK, 2008 | DUTCHMEN | AEROLITE, 2008 | DUTCHMEN | ARISTOCRAT, 2008 | DUTCHMEN | BAYRIDGE, 2008 | DUTCHMEN | BRECKENRIDGE, 2008 | DUTCHMEN | COLORADO, 2008 | DUTCHMEN | DENALI, 2008 | DUTCHMEN | DUTCHMEN, 2008 | DUTCHMEN | ECO, 2008 | DUTCHMEN | FOUR WINDS, 2008 | DUTCHMEN | FREEDOM SPIRIT, 2008 | DUTCHMEN | GRAND JUNCITON, 2008 | DUTCHMEN | KODIAK, 2008 | DUTCHMEN | KOMFORT, 2008 | DUTCHMEN | MONTE VISTA, 2008 | DUTCHMEN | N'TENSE, 2008 | DUTCHMEN | NORTHSHORE, 2008 | DUTCHMEN | RAINER, 2008 | DUTCHMEN | SPORT, 2008 | DUTCHMEN | T@B, 2008 | DUTCHMEN | T@DA, 2008 | DUTCHMEN | TUNDRA, 2008 | DUTCHMEN | VICTORY LANE, 2008 | DUTCHMEN | WILD THING, 2008 | DUTCHMEN | WINNERS CIRCLE, 2008 | DUTCHMEN | ZOOM, 2008 | KEYSTONE | CHALLENGER, 2008 | KEYSTONE | COUGAR, 2008 | KEYSTONE | ENERGY, 2008 | KEYSTONE | EVEREST, 2008 | KEYSTONE | FREEDOM ELITE, 2008 | KEYSTONE | FREEDOMLITE, 2008 | KEYSTONE | FUZION, 2008 | KEYSTONE | HIDEOUT, 2008 | KEYSTONE | HORNET, 2008 | KEYSTONE | HORNET RETREAT, 2008 | KEYSTONE | LAREDO, 2008 | KEYSTONE | MONTANA, 2008 | KEYSTONE | MONTANA BIG SKY, 2008 | KEYSTONE | MONTANA MOUNTAINEER, 2008 | KEYSTONE | OUTBACK, 2008 | KEYSTONE | OUTBACK SYDNEY, 2008 | KEYSTONE | PASSPORT, 2008 | KEYSTONE | RAPTOR, 2008 | KEYSTONE | SPRINGDALE, 2008 | KEYSTONE | SPRINGDALE SUMMERLAND, 2008 | KEYSTONE | SPRINTER, 2008 | KEYSTONE | VR1, 2009 | CROSSROADS | CROSS TERRAIN, 2009 | CROSSROADS | CROSSFORCE, 2009 | CROSSROADS | CRUISER, 2009 | CROSSROADS | HAMPTON, 2009 | CROSSROADS | KINGSTON, 2009 | CROSSROADS | SEVILLE, 2009 | CROSSROADS | SIMPLICITY, 2009 | CROSSROADS | SLINGSHOT, 2009 | CROSSROADS | SUNSET TRAIL, 2009 | CROSSROADS | WESTCHESTER, 2009 | CROSSROADS | ZINGER, 2009 | DUTCHMEN | ADIRONDACK, 2009 | DUTCHMEN | AEROLITE, 2009 | DUTCHMEN | ARISTOCRAT, 2009 | DUTCHMEN | BAYRIDGE, 2009 | DUTCHMEN | BRECKENRIDGE, 2009 | DUTCHMEN | COLORADO, 2009 | DUTCHMEN | CUB, 2009 | DUTCHMEN | DENALI, 2009 | DUTCHMEN | DUTCHLITE, 2009 | DUTCHMEN | DUTCHMEN, 2009 | DUTCHMEN | ECO, 2009 | DUTCHMEN | FOUR WINDS, 2009 | DUTCHMEN | FREEDOM SPIRIT, 2009 | DUTCHMEN | GRAND JUNCITON, 2009 | DUTCHMEN | KODIAK, 2009 | DUTCHMEN | KOMFORT, 2009 | DUTCHMEN | MONTE VISTA, 2009 | DUTCHMEN | N'TENSE, 2009 | DUTCHMEN | NORTHSHORE, 2009 | DUTCHMEN | RAINER, 2009 | DUTCHMEN | SPORT, 2009 | DUTCHMEN | T@B, 2009 | DUTCHMEN | T@DA, 2009 | DUTCHMEN | T@G, 2009 | DUTCHMEN | TOPO, 2009 | DUTCHMEN | TUNDRA, 2009 | DUTCHMEN | VICTORY LANE, 2009 | DUTCHMEN | WINNERS CIRCLE, 2009 | DUTCHMEN | ZOOM, 2009 | KEYSTONE | BULLET, 2009 | KEYSTONE | CHALLENGER, 2009 | KEYSTONE | COUGAR, 2009 | KEYSTONE | ENERGY, 2009 | KEYSTONE | EVEREST, 2009 | KEYSTONE | FREEDOM ELITE, 2009 | KEYSTONE | FREEDOMLITE, 2009 | KEYSTONE | FUZION, 2009 | KEYSTONE | HIDEOUT, 2009 | KEYSTONE | HORNET, 2009 | KEYSTONE | LAREDO, 2009 | KEYSTONE | MONTANA, 2009 | KEYSTONE | MONTANA BIG SKY, 2009 | KEYSTONE | OUTBACK, 2009 | KEYSTONE | PASSPORT, 2009 | KEYSTONE | RAPTOR, 2009 | KEYSTONE | RESIDENCE, 2009 | KEYSTONE | SPRINGDALE, 2009 | KEYSTONE | SPRINTER, 2009 | KEYSTONE | VR1, 2010 | CROSSROADS | CRUISER, 2010 | CROSSROADS | HAMPTON, 2010 | CROSSROADS | KINGSTON, 2010 | CROSSROADS | SEVILLE, 2010 | CROSSROADS | SIMPLICITY, 2010 | CROSSROADS | SLINGSHOT, 2010 | CROSSROADS | SUNSET TRAIL, 2010 | CROSSROADS | WESTCHESTER, 2010 | CROSSROADS | ZINGER, 2010 | DUTCHMEN | AEROLITE, 2010 | DUTCHMEN | ARISTOCRAT, 2010 | DUTCHMEN | BAYRIDGE, 2010 | DUTCHMEN | BRECKENRIDGE, 2010 | DUTCHMEN | COLEMAN, 2010 | DUTCHMEN | COLORADO, 2010 | DUTCHMEN | CUB, 2010 | DUTCHMEN | DENALI, 2010 | DUTCHMEN | DUTCHLITE, 2010 | DUTCHMEN | DUTCHMEN, 2010 | DUTCHMEN | ECO, 2010 | DUTCHMEN | FOUR WINDS, 2010 | DUTCHMEN | FREEDOM SPIRIT, 2010 | DUTCHMEN | GRAND JUNCITON, 2010 | DUTCHMEN | KODIAK, 2010 | DUTCHMEN | KOMFORT, 2010 | DUTCHMEN | N'TENSE, 2010 | DUTCHMEN | NORTHSHORE, 2010 | DUTCHMEN | RAINER, 2010 | DUTCHMEN | SPORT, 2010 | DUTCHMEN | T@B, 2010 | DUTCHMEN | T@DA, 2010 | DUTCHMEN | TOPO, 2010 | DUTCHMEN | ZOOM, 2010 | KEYSTONE | ALPINE, 2010 | KEYSTONE | AVALANCHE, 2010 | KEYSTONE | BULLET, 2010 | KEYSTONE | CHALLENGER, 2010 | KEYSTONE | COUGAR, 2010 | KEYSTONE | ENERGY, 2010 | KEYSTONE | EVEREST, 2010 | KEYSTONE | FUZION, 2010 | KEYSTONE | HIDEOUT, 2010 | KEYSTONE | HORNET, 2010 | KEYSTONE | LAREDO, 2010 | KEYSTONE | MONTANA, 2010 | KEYSTONE | MONTANA BIG SKY, 2010 | KEYSTONE | OUTBACK, 2010 | KEYSTONE | PASSPORT, 2010 | KEYSTONE | RAPTOR, 2010 | KEYSTONE | RESIDENCE, 2010 | KEYSTONE | RETREAT, 2010 | KEYSTONE | SPRINGDALE, 2010 | KEYSTONE | SPRINTER, 2010 | KEYSTONE | VR1, 2011 | CROSSROADS | COMMERCIAL DUTY, 2011 | CROSSROADS | CRUISER, 2011 | CROSSROADS | HAMPTON, 2011 | CROSSROADS | KINGSTON, 2011 | CROSSROADS | LIL'-CABIN, 2011 | CROSSROADS | REDWOOD, 2011 | CROSSROADS | RUSHMORE, 2011 | CROSSROADS | SEVILLE, 2011 | CROSSROADS | SLINGSHOT, 2011 | CROSSROADS | SUNSET TRAIL, 2011 | CROSSROADS | WESTCHESTER, 2011 | CROSSROADS | ZINGER, 2011 | DUTCHMEN | AEROLITE, 2011 | DUTCHMEN | APREN TRAIL, 2011 | DUTCHMEN | BAYRIDGE, 2011 | DUTCHMEN | BRECKENRIDGE, 2011 | DUTCHMEN | COLEMAN, 2011 | DUTCHMEN | COLORADO, 2011 | DUTCHMEN | DENALI, 2011 | DUTCHMEN | DUTCHMEN, 2011 | DUTCHMEN | FOUR WINDS, 2011 | DUTCHMEN | GRAND JUNCITON, 2011 | DUTCHMEN | KODIAK, 2011 | DUTCHMEN | KOMFORT, 2011 | DUTCHMEN | LAKEWOOD, 2011 | DUTCHMEN | RAINER, 2011 | DUTCHMEN | RUBICON, 2011 | DUTCHMEN | VOLTAGE, 2011 | KEYSTONE | ALPINE, 2011 | KEYSTONE | AVALANCHE, 2011 | KEYSTONE | BULLET, 2011 | KEYSTONE | COUGAR, 2011 | KEYSTONE | ENERGY, 2011 | KEYSTONE | FUZION, 2011 | KEYSTONE | HIDEOUT, 2011 | KEYSTONE | HORNET, 2011 | KEYSTONE | LAREDO, 2011 | KEYSTONE | MONTANA, 2011 | KEYSTONE | MONTANA BIG SKY, 2011 | KEYSTONE | OUTBACK, 2011 | KEYSTONE | PASSPORT, 2011 | KEYSTONE | RAPTOR, 2011 | KEYSTONE | RESIDENCE, 2011 | KEYSTONE | RETREAT, 2011 | KEYSTONE | SPRINGDALE, 2011 | KEYSTONE | SPRINTER, 2012 | CROSSROADS | BLACKWOOD, 2012 | CROSSROADS | CRUISER, 2012 | CROSSROADS | ELEVATION, 2012 | CROSSROADS | HAMPTON, 2012 | CROSSROADS | HILL COUNTRY, 2012 | CROSSROADS | REDWOOD, 2012 | CROSSROADS | RUSHMORE, 2012 | CROSSROADS | SLINGSHOT, 2012 | CROSSROADS | SUNSET TRAIL, 2012 | CROSSROADS | Z1, 2012 | CROSSROADS | ZINGER, 2012 | DUTCHMEN | AEROLITE, 2012 | DUTCHMEN | APREN TRAIL, 2012 | DUTCHMEN | BAYRIDGE, 2012 | DUTCHMEN | BRECKENRIDGE, 2012 | DUTCHMEN | COLEMAN, 2012 | DUTCHMEN | DENALI, 2012 | DUTCHMEN | DUTCHMEN, 2012 | DUTCHMEN | INFINITY, 2012 | DUTCHMEN | KODIAK, 2012 | DUTCHMEN | KOMFORT, 2012 | DUTCHMEN | LAKEWOOD, 2012 | DUTCHMEN | RAZORBACK, 2012 | DUTCHMEN | RUBICON, 2012 | DUTCHMEN | VOLTAGE, 2012 | KEYSTONE | ALPINE, 2012 | KEYSTONE | AVALANCHE, 2012 | KEYSTONE | BULLET, 2012 | KEYSTONE | COUGAR, 2012 | KEYSTONE | ENERGY, 2012 | KEYSTONE | FUZION, 2012 | KEYSTONE | HIDEOUT, 2012 | KEYSTONE | HORNET, 2012 | KEYSTONE | LAREDO, 2012 | KEYSTONE | MONTANA, 2012 | KEYSTONE | MONTANA BIG SKY, 2012 | KEYSTONE | OUTBACK, 2012 | KEYSTONE | PASSPORT, 2012 | KEYSTONE | RAPTOR, 2012 | KEYSTONE | RESIDENCE, 2012 | KEYSTONE | RETREAT, 2012 | KEYSTONE | SPRINGDALE, 2012 | KEYSTONE | SPRINTER, 2012 | KEYSTONE | VANTAGE, 2013 | CROSSROADS | BLACKWOOD, 2013 | CROSSROADS | CRUISER, 2013 | CROSSROADS | ELEVATION, 2013 | CROSSROADS | HAMPTON, 2013 | CROSSROADS | HILL COUNTRY, 2013 | CROSSROADS | LONGHORN, 2013 | CROSSROADS | MAPLE COUNTRY, 2013 | CROSSROADS | REDWOOD, 2013 | CROSSROADS | RUSHMORE, 2013 | CROSSROADS | SLINGSHOT, 2013 | CROSSROADS | SUNSET TRAIL, 2013 | CROSSROADS | Z1, 2013 | CROSSROADS | ZINGER, 2013 | DUTCHMEN | AEROLITE, 2013 | DUTCHMEN | APREN TRAIL, 2013 | DUTCHMEN | BAYRIDGE, 2013 | DUTCHMEN | BRECKENRIDGE, 2013 | DUTCHMEN | COLEMAN, 2013 | DUTCHMEN | DENALI, 2013 | DUTCHMEN | DUTCHMEN, 2013 | DUTCHMEN | INFINITY, 2013 | DUTCHMEN | KODIAK, 2013 | DUTCHMEN | KOMFORT, 2013 | DUTCHMEN | RAZORBACK, 2013 | DUTCHMEN | RUBICON, 2013 | DUTCHMEN | VOLTAGE, 2013 | KEYSTONE | ALPINE, 2013 | KEYSTONE | AVALANCHE, 2013 | KEYSTONE | BULLET, 2013 | KEYSTONE | COUGAR, 2013 | KEYSTONE | ENERGY, 2013 | KEYSTONE | FUZION, 2013 | KEYSTONE | HIDEOUT, 2013 | KEYSTONE | HORNET, 2013 | KEYSTONE | LAREDO, 2013 | KEYSTONE | MONTANA, 2013 | KEYSTONE | MONTANA BIG SKY, 2013 | KEYSTONE | OUTBACK, 2013 | KEYSTONE | PASSPORT, 2013 | KEYSTONE | RAPTOR, 2013 | KEYSTONE | RESIDENCE, 2013 | KEYSTONE | RETREAT, 2013 | KEYSTONE | SPRINGDALE, 2013 | KEYSTONE | SPRINTER, 2013 | KEYSTONE | VANTAGE, 2014 | CROSSROADS | ALTITUDE, 2014 | CROSSROADS | CRUISER, 2014 | CROSSROADS | ELEVATION, 2014 | CROSSROADS | HAMPTON, 2014 | CROSSROADS | HILL COUNTRY, 2014 | CROSSROADS | LONGHORN, 2014 | CROSSROADS | LONGHORN REZERVE, 2014 | CROSSROADS | MAPLE COUNTRY, 2014 | CROSSROADS | REDWOOD, 2014 | CROSSROADS | REZERVE, 2014 | CROSSROADS | RUSHMORE, 2014 | CROSSROADS | SUNSET TRAIL, 2014 | CROSSROADS | Z1, 2014 | CROSSROADS | ZINGER, 2014 | DUTCHMEN | AEROLITE, 2014 | DUTCHMEN | APREN TRAIL, 2014 | DUTCHMEN | BRECKENRIDGE, 2014 | DUTCHMEN | COLEMAN, 2014 | DUTCHMEN | DENALI, 2014 | DUTCHMEN | DUTCHMEN, 2014 | DUTCHMEN | INFINITY, 2014 | DUTCHMEN | KODIAK, 2014 | DUTCHMEN | KOMFORT, 2014 | DUTCHMEN | RAZORBACK, 2014 | DUTCHMEN | RUBICON, 2014 | DUTCHMEN | VOLTAGE, 2014 | KEYSTONE | ALPINE, 2014 | KEYSTONE | AVALANCHE, 2014 | KEYSTONE | BULLET, 2014 | KEYSTONE | CARBON, 2014 | KEYSTONE | COUGAR, 2014 | KEYSTONE | ENERGY, 2014 | KEYSTONE | FUZION, 2014 | KEYSTONE | HIDEOUT, 2014 | KEYSTONE | HORNET, 2014 | KEYSTONE | IMPACT, 2014 | KEYSTONE | LAREDO, 2014 | KEYSTONE | MONTANA, 2014 | KEYSTONE | MONTANA BIG SKY, 2014 | KEYSTONE | OUTBACK, 2014 | KEYSTONE | PASSPORT, 2014 | KEYSTONE | RAPTOR, 2014 | KEYSTONE | RESIDENCE, 2014 | KEYSTONE | RETREAT, 2014 | KEYSTONE | SPRINGDALE, 2014 | KEYSTONE | SPRINTER, 2015 | CROSSROADS | ALTITUDE, 2015 | CROSSROADS | CAMEO, 2015 | CROSSROADS | CARRIAGE, 2015 | CROSSROADS | CRUISER, 2015 | CROSSROADS | CYPRESS, 2015 | CROSSROADS | ELEVATION, 2015 | CROSSROADS | HAMPTON, 2015 | CROSSROADS | HILL COUNTRY, 2015 | CROSSROADS | ICE SEEKER, 2015 | CROSSROADS | LONGHORN, 2015 | CROSSROADS | LONGHORN REZERVE, 2015 | CROSSROADS | MAPLE COUNTRY, 2015 | CROSSROADS | REDWOOD, 2015 | CROSSROADS | REZERVE, 2015 | CROSSROADS | RUSHMORE, 2015 | CROSSROADS | SEQUOIA, 2015 | CROSSROADS | SUNSET TRAIL, 2015 | CROSSROADS | Z1, 2015 | CROSSROADS | ZINGER, 2015 | DUTCHMEN | AEROLITE, 2015 | DUTCHMEN | APREN TRAIL, 2015 | DUTCHMEN | COLEMAN, 2015 | DUTCHMEN | DENALI, 2015 | DUTCHMEN | DUTCHMEN, 2015 | DUTCHMEN | KODIAK, 2015 | DUTCHMEN | RAZORBACK, 2015 | DUTCHMEN | RUBICON, 2015 | DUTCHMEN | VOLTAGE, 2015 | KEYSTONE | ALPINE, 2015 | KEYSTONE | AVALANCHE, 2015 | KEYSTONE | BULLET, 2015 | KEYSTONE | CARBON, 2015 | KEYSTONE | COUGAR, 2015 | KEYSTONE | ENERGY, 2015 | KEYSTONE | FUZION, 2015 | KEYSTONE | HIDEOUT, 2015 | KEYSTONE | IMPACT, 2015 | KEYSTONE | INFINITY, 2015 | KEYSTONE | LAREDO, 2015 | KEYSTONE | MONTANA, 2015 | KEYSTONE | MONTANA BIG SKY, 2015 | KEYSTONE | OUTBACK, 2015 | KEYSTONE | PASSPORT, 2015 | KEYSTONE | RAPTOR, 2015 | KEYSTONE | RESIDENCE, 2015 | KEYSTONE | RETREAT, 2015 | KEYSTONE | SPRINGDALE, 2015 | KEYSTONE | SPRINTER, 2016 | CROSSROADS | ALTITUDE, 2016 | CROSSROADS | CAMEO, 2016 | CROSSROADS | CARRIAGE, 2016 | CROSSROADS | CRUISER, 2016 | CROSSROADS | CYPRESS, 2016 | CROSSROADS | ELEVATION, 2016 | CROSSROADS | HAMPTON, 2016 | CROSSROADS | HILL COUNTRY, 2016 | CROSSROADS | LONGHORN, 2016 | CROSSROADS | LONGHORN REZERVE, 2016 | CROSSROADS | MAPLE COUNTRY, 2016 | CROSSROADS | REDWOOD, 2016 | CROSSROADS | REZERVE, 2016 | CROSSROADS | RUSHMORE, 2016 | CROSSROADS | SEQUOIA, 2016 | CROSSROADS | SUNSET TRAIL, 2016 | CROSSROADS | Z1, 2016 | CROSSROADS | ZINGER, 2016 | DUTCHMEN | AEROLITE, 2016 | DUTCHMEN | APREN TRAIL, 2016 | DUTCHMEN | COLEMAN, 2016 | DUTCHMEN | DENALI, 2016 | DUTCHMEN | KODIAK, 2016 | DUTCHMEN | RAZORBACK, 2016 | DUTCHMEN | RUBICON, 2016 | DUTCHMEN | VOLTAGE, 2016 | KEYSTONE | ALPINE, 2016 | KEYSTONE | AVALANCHE, 2016 | KEYSTONE | BULLET, 2016 | KEYSTONE | CARBON, 2016 | KEYSTONE | COUGAR, 2016 | KEYSTONE | FUZION, 2016 | KEYSTONE | HIDEOUT, 2016 | KEYSTONE | IMPACT, 2016 | KEYSTONE | LAREDO, 2016 | KEYSTONE | MONTANA, 2016 | KEYSTONE | OUTBACK, 2016 | KEYSTONE | PASSPORT, 2016 | KEYSTONE | RAPTOR, 2016 | KEYSTONE | RESIDENCE, 2016 | KEYSTONE | RETREAT, 2016 | KEYSTONE | SPRINGDALE, 2016 | KEYSTONE | SPRINTER, 2017 | CROSSROADS | ALTITUDE, 2017 | CROSSROADS | CAMEO, 2017 | CROSSROADS | CARRIAGE, 2017 | CROSSROADS | CRUISER, 2017 | CROSSROADS | HAMPTON, 2017 | CROSSROADS | HILL COUNTRY, 2017 | CROSSROADS | LONGHORN, 2017 | CROSSROADS | LONGHORN REZERVE, 2017 | CROSSROADS | MAPLE COUNTRY, 2017 | CROSSROADS | REDWOOD, 2017 | CROSSROADS | REZERVE, 2017 | CROSSROADS | SEQUOIA, 2017 | CROSSROADS | SUNSET TRAIL, 2017 | CROSSROADS | TRANQUILITY, 2017 | CROSSROADS | VOLANTE, 2017 | CROSSROADS | Z1, 2017 | CROSSROADS | ZINGER, 2017 | DUTCHMEN | AEROLITE, 2017 | DUTCHMEN | APREN TRAIL, 2017 | DUTCHMEN | COLEMAN, 2017 | DUTCHMEN | DENALI, 2017 | DUTCHMEN | KODIAK, 2017 | DUTCHMEN | RAZORBACK, 2017 | DUTCHMEN | RUBICON, 2017 | DUTCHMEN | VOLTAGE, 2017 | KEYSTONE | ALPINE, 2017 | KEYSTONE | AVALANCHE, 2017 | KEYSTONE | BULLET, 2017 | KEYSTONE | CARBON, 2017 | KEYSTONE | COUGAR, 2017 | KEYSTONE | FUZION, 2017 | KEYSTONE | HIDEOUT, 2017 | KEYSTONE | IMPACT, 2017 | KEYSTONE | LAREDO, 2017 | KEYSTONE | MONTANA, 2017 | KEYSTONE | OUTBACK, 2017 | KEYSTONE | PASSPORT, 2017 | KEYSTONE | RAPTOR, 2017 | KEYSTONE | RESIDENCE, 2017 | KEYSTONE | RETREAT, 2017 | KEYSTONE | SPRINGDALE, 2017 | KEYSTONE | SPRINTER, 2018 | CROSSROADS | CAMEO, 2018 | CROSSROADS | CRUISER, 2018 | CROSSROADS | HAMPTON, 2018 | CROSSROADS | LONGHORN, 2018 | CROSSROADS | REDWOOD, 2018 | CROSSROADS | SUNSET TRAIL, 2018 | CROSSROADS | TRANQUILITY, 2018 | CROSSROADS | VOLANTE, 2018 | CROSSROADS | ZINGER, 2018 | DUTCHMEN | AEROLITE, 2018 | DUTCHMEN | APREN TRAIL, 2018 | DUTCHMEN | ATLAS, 2018 | DUTCHMEN | COLEMAN, 2018 | DUTCHMEN | DENALI, 2018 | DUTCHMEN | ENDURANCE, 2018 | DUTCHMEN | KODIAK, 2018 | DUTCHMEN | RUBICON, 2018 | DUTCHMEN | VOLTAGE, 2018 | KEYSTONE | ALPINE, 2018 | KEYSTONE | AVALANCHE, 2018 | KEYSTONE | BULLET, 2018 | KEYSTONE | CARBON, 2018 | KEYSTONE | COUGAR, 2018 | KEYSTONE | FUZION, 2018 | KEYSTONE | HIDEOUT, 2018 | KEYSTONE | IMPACT, 2018 | KEYSTONE | LAREDO, 2018 | KEYSTONE | MONTANA, 2018 | KEYSTONE | OUTBACK, 2018 | KEYSTONE | PASSPORT, 2018 | KEYSTONE | RAPTOR, 2018 | KEYSTONE | RESIDENCE, 2018 | KEYSTONE | RETREAT, 2018 | KEYSTONE | SPRINGDALE, 2018 | KEYSTONE | SPRINTER

Problème

Dans certains véhicules munis d'extincteurs Kidde à poignée et à robinet en plastique noir, les extincteurs pourraient se boucher ou nécessiter une force excessive pour être actionnés. De plus, la buse pourrait se séparer du robinet avec assez de force pour causer des blessures, et empêcher le fonctionnement de l'extincteur. En cas d'incendie, une défaillance de l'extincteur pourrait causer des blessures ou des dommages matériels (ou les deux). Mesure corrective : Les propriétaires recevront des instructions sur la manière d'inspecter l'extincteur afin de vérifier s'il fait l'objet d'un rappel. Des extincteurs de rechange seront fournis directement par Kidde. Remarque : Pour obtenir de plus amples renseignements sur les extincteurs faisant l'objet d'un rappel, veuillez consulter le site Web suivant : www.kidde.com.

Renseignements supplémentaires

Contexte

Vous pouvez trouver le rappel d’origine dans la Banque de données des rappels de sécurité automobile de Transports Canada.

Détails
Date de publication originale :
Type d’avis ou de rappel
Rappel de véhicule
Catégorie
Véhicules - Autocaravane
Entreprises
Publié par
Transports Canada
Auditoire
Grand public
Numéro d’identification
RA-67861
Transports Canada Identifiant (ID)
2017627