Consumer product recall

Archived - Effikal Automatic Gas Vent Dampers

Starting date:
November 1, 2008
Posting date:
November 1, 2008
Type of communication:
Consumer Product Recall
Subcategory:
Household Items
Source of recall:
Health Canada
Issue:
Product Safety, Poisoning Hazard
Audience:
General Public
Identification number:
RA-500001828

Affected products

Effikal Automatic Gas Vent Dampers

Product description

The recall involves Effikal RVGP-PC Gas Vent Dampers sizes 4, 5, 6, 7, 8, 9 or 10 inch that are installed with gas boiler systems listed below.
Manufacturer Atmospheric Gas Boiler Models Vent Damper Date Codes Vent Damper Serial Numbers
Allied Engineering MG, MS and SG Series 0728 through 0809 3588428 through 3687571
Burnham Series 2b, Series 8h, and Independence except Independence PV 0728-0738 3588428-3647820
Crown AWI, CWI and BSI Series 0728-0809 3588428-3687571
Laars JV Series 0728-0809 3588428-3687571
Lochinvar CBN Solution Series 0728-0809 3588428-3687571
RBI Spectrum Series 0728-0809 3588428-3687571
Smith GB and HW Series 0728-0809 3588428-3687571
New Yorker CG and CGS Series 0728-0738 3588428-3647827
Peerless MI, 63 and GM series 0728-0809 3588428-3687571
Raypak Series XV-42-180 Series V-181-260 and 182-261 Series VII-133 0728-0809 3588428-3687571
Union Steam GWA and GSA 0728-0809 3588428-3687571
Weil-McLain CGa, EG, and PFG Series 0728-0738 3588428-3647830
WilliamsonThermoflo GWA and GSA s 0728-0738 3588428-3647831

The vent damper date code is located on a sticker under the motor assembly cap on the plastic base. Serial numbers are located on a label on the side of the damper's cap.

All sizes and models of the RVGP-PC have the same motor assembly with black Effikal caps and black plastic bases.

Hazard identified

The dampers have, in some cases developed cracks on the plastic ears connecting the motor assembly to the mounting bracket. If both ears break, the motor assembly could disconnect from the bracket. Such a failure of the motor assembly combined with a failure of the appliance blocked vent switch could result in a carbon monoxide (CO) leak, posing a risk of CO poisoning.

No incidents or injuries have been reported by the US manufacturer, Effikal LLC.

Health Canada has not received any reports of incidents or injuries to Canadians related to the use of these Gas Vent Dampers.

Number sold

Approximately 5,000 Effikal Automatic Gas Vent Dampers were sold in Canada.

Time period sold

The recalled gas vent dampers were sold from August 2007 to July 2008.

Place of origin

Manufactured in United States.

Companies

Manufacturer

Effikal LLC

Orion

Michigan

UNITED STATES

Images (select thumbnail to enlarge - opens in a new window)


What you should do

Consumers should immediately stop using the Automatic Gas Vent Dampers.

Consumers may contact their installer as soon as possible to confirm they have a recalled vent damper and to receive a free vent damper replacement.

For additional information, contact Effikal toll-free at (866) 790-3739, or visit the firm's Web site.