Numéro de rappel de Transports Canada - 2017649 - JAYCO
Marque(s)
Résumé
Veuillez consulter la section des mesures correctives ci-dessous
Produits visés
2002 | JAYCO | COVE TRAVEL TRAILER, 2002 | JAYCO | DESIGNER FIFTH WHEEL TRAILER, 2002 | JAYCO | EAGLE FIFTH WHEEL TRAILER, 2002 | JAYCO | EAGLE FOLDING CAMPING TRAILER, 2002 | JAYCO | EAGLE TRAVEL TRAILER, 2002 | JAYCO | FIRENZA MOTORHOME, 2002 | JAYCO | GRANITE RIDGE MOTORHOME, 2002 | JAYCO | HERITAGE FOLDING CAMPING TRAILER, 2002 | JAYCO | JAY FLIGHT FIFTH WHEEL TRAILER, 2002 | JAYCO | JAY FLIGHT TRAVEL TRAILER, 2002 | JAYCO | KIWI TRAVEL TRAILER, 2002 | JAYCO | LEGACY FIFTH WHEEL TRAILER, 2002 | JAYCO | QWEST CAMPING TRAILER, 2002 | JAYCO | QWEST TRAVEL TRAILER, 2002 | JAYCO | TALON TRAVEL TRAILER, 2003 | JAYCO | AVATAR MOTORHOME, 2003 | JAYCO | COVE TRAVEL TRAILER, 2003 | JAYCO | DESIGNER CAMPING TRAILER, 2003 | JAYCO | DESIGNER TRAVEL TRAILER, 2003 | JAYCO | EAGLE FIFTH WHEEL TRAILER, 2003 | JAYCO | EAGLE FOLDING CAMPING TRAILER, 2003 | JAYCO | EAGLE TRAVEL TRAILER, 2003 | JAYCO | ESCAPADE MOTORHOME, 2003 | JAYCO | FIRENZA MOTORHOME, 2003 | JAYCO | GRANITE RIDGE MOTORHOME, 2003 | JAYCO | GREYHAWK MOTORHOME, 2003 | JAYCO | JAY FLIGHT FIFTH WHEEL TRAILER, 2003 | JAYCO | JAY FLIGHT TRAVEL TRAILER, 2003 | JAYCO | KIWI TRAVEL TRAILER, 2003 | JAYCO | LEGACY FIFTH WHEEL TRAILER, 2003 | JAYCO | QWEST CAMPING TRAILER, 2003 | JAYCO | QWEST FIFTH WHEEL TRAILER, 2003 | JAYCO | QWEST TRAVEL TRAILER, 2003 | JAYCO | TALON FIFTH WHEEL TRAILER, 2003 | JAYCO | TALON TRAVEL TRAILER, 2004 | JAYCO | AMBIENT MOTORHOME, 2004 | JAYCO | COVE TRAVEL TRAILER, 2004 | JAYCO | DESIGNER CAMPING TRAILER, 2004 | JAYCO | DESIGNER TRAVEL TRAILER, 2004 | JAYCO | EAGLE FIFTH WHEEL TRAILER, 2004 | JAYCO | EAGLE FOLDING CAMPING TRAILER, 2004 | JAYCO | EAGLE TRAVEL TRAILER, 2004 | JAYCO | ESCAPADE MOTORHOME, 2004 | JAYCO | GRANITE RIDGE MOTORHOME, 2004 | JAYCO | GREYHAWK MOTORHOME, 2004 | JAYCO | JAY FEATHER TRAVEL TRAILER, 2004 | JAYCO | JAY FLIGHT FIFTH WHEEL TRAILER, 2004 | JAYCO | JAY FLIGHT TRAVEL TRAILER, 2004 | JAYCO | LEGACY FIFTH WHEEL TRAILER, 2004 | JAYCO | QWEST CAMPING TRAILER, 2004 | JAYCO | TALON FIFTH WHEEL TRAILER, 2004 | JAYCO | TALON TRAVEL TRAILER, 2005 | JAYCO | AMBIENT MOTORHOME, 2005 | JAYCO | BAJA CAMPING TRAILER, 2005 | JAYCO | COVE TRAVEL TRAILER, 2005 | JAYCO | DESIGNER FIFTH WHEEL TRAILER, 2005 | JAYCO | EAGLE FIFTH WHEEL TRAILER, 2005 | JAYCO | EAGLE TRAVEL TRAILER, 2005 | JAYCO | ESCAPADE MOTORHOME, 2005 | JAYCO | GRANITE RIDGE MOTORHOME, 2005 | JAYCO | GREYHAWK MOTORHOME, 2005 | JAYCO | JAY FEATHER TRAVEL TRAILER, 2005 | JAYCO | JAY FLIGHT FIFTH WHEEL TRAILER, 2005 | JAYCO | JAY FLIGHT TRAVEL TRAILER, 2005 | JAYCO | JAY SERIES, 2005 | JAYCO | SENECA CLASS C MOTORHOME, 2005 | JAYCO | TALON FIFTH WHEEL TRAILER, 2005 | JAYCO | TALON TRAVEL TRAILER, 2006 | JAYCO | ESCAPADE MOTORHOME, 2006 | JAYCO | GRANITE RIDGE MOTORHOME, 2006 | JAYCO | GREYHAWK MOTORHOME, 2006 | JAYCO | JAY FLIGHT FIFTH WHEEL TRAILER, 2006 | JAYCO | JAY FLIGHT TRAVEL TRAILER, 2006 | JAYCO | SENECA CLASS C MOTORHOME, 2006 | JAYCO | TALON FIFTH WHEEL TRAILER, 2006 | JAYCO | TALON TRAVEL TRAILER, 2007 | JAYCO | GREYHAWK MOTORHOME, 2007 | JAYCO | JAY FLIGHT TRAVEL TRAILER, 2007 | JAYCO | MELBOURNE, 2007 | JAYCO | SENECA CLASS C MOTORHOME, 2008 | JAYCO | BAJA CAMPING TRAILER, 2008 | JAYCO | DESIGNER FIFTH WHEEL TRAILER, 2008 | JAYCO | EAGLE FIFTH WHEEL TRAILER, 2008 | JAYCO | EAGLE TRAVEL TRAILER, 2008 | JAYCO | GREYHAWK MOTORHOME, 2008 | JAYCO | JAY FEATHER TRAVEL TRAILER, 2008 | JAYCO | JAY FLIGHT TRAVEL TRAILER, 2008 | JAYCO | JAY SERIES, 2008 | JAYCO | MELBOURNE, 2008 | JAYCO | OCTANE TRAVEL TRAILER, 2008 | JAYCO | RECON FIFTH WHEEL TRAILER, 2008 | JAYCO | SENECA CLASS C MOTORHOME, 2009 | JAYCO | BAJA CAMPING TRAILER, 2009 | JAYCO | DESIGNER FIFTH WHEEL TRAILER, 2009 | JAYCO | EAGLE FIFTH WHEEL TRAILER, 2009 | JAYCO | EMBARK, 2009 | JAYCO | GREYHAWK MOTORHOME, 2009 | JAYCO | JAY FEATHER TRAVEL TRAILER, 2009 | JAYCO | JAY FLIGHT TRAVEL TRAILER, 2009 | JAYCO | JAY SERIES, 2009 | JAYCO | MELBOURNE, 2009 | JAYCO | RECON FIFTH WHEEL TRAILER, 2009 | JAYCO | SENECA CLASS C MOTORHOME, 2010 | JAYCO | DESIGNER FIFTH WHEEL TRAILER, 2010 | JAYCO | EAGLE TRAVEL TRAILER, 2010 | JAYCO | EMBARK, 2010 | JAYCO | GREYHAWK MOTORHOME, 2010 | JAYCO | JAY FEATHER TRAVEL TRAILER, 2010 | JAYCO | JAY FLIGHT TRAVEL TRAILER, 2010 | JAYCO | JAY SERIES, 2010 | JAYCO | MELBOURNE, 2010 | JAYCO | NORTH POINT FIFTH WHEEL TRAILER, 2010 | JAYCO | OCTANE TRAVEL TRAILER, 2010 | JAYCO | PRECEPT MOTORHOME, 2010 | JAYCO | RECON FIFTH WHEEL TRAILER, 2010 | JAYCO | SENECA CLASS C MOTORHOME, 2011 | JAYCO | EAGLE TRAVEL TRAILER, 2011 | JAYCO | GREYHAWK MOTORHOME, 2011 | JAYCO | JAY FEATHER TRAVEL TRAILER, 2011 | JAYCO | JAY FLIGHT TRAVEL TRAILER, 2011 | JAYCO | JAY SERIES, 2011 | JAYCO | MELBOURNE, 2011 | JAYCO | OCTANE TRAVEL TRAILER, 2011 | JAYCO | SENECA CLASS C MOTORHOME, 2011 | JAYCO | SKYLARK TRAVEL TRAILER, 2012 | JAYCO | EAGLE FIFTH WHEEL TRAILER, 2012 | JAYCO | EAGLE TRAVEL TRAILER, 2012 | JAYCO | EMBARK, 2012 | JAYCO | GREYHAWK MOTORHOME, 2012 | JAYCO | JAY FEATHER TRAVEL TRAILER, 2012 | JAYCO | JAY FLIGHT TRAVEL TRAILER, 2012 | JAYCO | JAY SERIES, 2012 | JAYCO | MELBOURNE, 2012 | JAYCO | NORTH POINT FIFTH WHEEL TRAILER, 2012 | JAYCO | OCTANE TRAVEL TRAILER, 2012 | JAYCO | PINNACLE FIFTH WHEEL TRAILER, 2012 | JAYCO | SENECA CLASS C MOTORHOME, 2012 | JAYCO | SKYLARK TRAVEL TRAILER, 2012 | JAYCO | WHITE HAWK TRAVEL TRAILER, 2013 | JAYCO | EAGLE FIFTH WHEEL TRAILER, 2013 | JAYCO | EAGLE TRAVEL TRAILER, 2013 | JAYCO | GREYHAWK MOTORHOME, 2013 | JAYCO | JAY FEATHER TRAVEL TRAILER, 2013 | JAYCO | JAY FLIGHT TRAVEL TRAILER, 2013 | JAYCO | JAY SERIES, 2013 | JAYCO | MELBOURNE, 2013 | JAYCO | NORTH POINT FIFTH WHEEL TRAILER, 2013 | JAYCO | OCTANE TRAVEL TRAILER, 2013 | JAYCO | PINNACLE FIFTH WHEEL TRAILER, 2013 | JAYCO | SEISMIC FIFTH WHEEL TRAILER, 2013 | JAYCO | SENECA CLASS C MOTORHOME, 2013 | JAYCO | WHITE HAWK TRAVEL TRAILER, 2014 | JAYCO | EAGLE FIFTH WHEEL TRAILER, 2014 | JAYCO | EAGLE TRAVEL TRAILER, 2014 | JAYCO | GREYHAWK MOTORHOME, 2014 | JAYCO | JAY FEATHER TRAVEL TRAILER, 2014 | JAYCO | JAY FLIGHT TRAVEL TRAILER, 2014 | JAYCO | JAY SERIES, 2014 | JAYCO | MELBOURNE, 2014 | JAYCO | NORTH POINT FIFTH WHEEL TRAILER, 2014 | JAYCO | OCTANE TRAVEL TRAILER, 2014 | JAYCO | PINNACLE FIFTH WHEEL TRAILER, 2014 | JAYCO | PRECEPT MOTORHOME, 2014 | JAYCO | REDHAWK MOTORHOME, 2014 | JAYCO | SEISMIC FIFTH WHEEL TRAILER, 2014 | JAYCO | SENECA CLASS C MOTORHOME, 2014 | JAYCO | WHITE HAWK TRAVEL TRAILER, 2015 | JAYCO | EAGLE FIFTH WHEEL TRAILER, 2015 | JAYCO | EAGLE TRAVEL TRAILER, 2015 | JAYCO | GREYHAWK MOTORHOME, 2015 | JAYCO | JAY FEATHER TRAVEL TRAILER, 2015 | JAYCO | JAY FLIGHT TRAVEL TRAILER, 2015 | JAYCO | JAY SERIES, 2015 | JAYCO | MELBOURNE, 2015 | JAYCO | NORTH POINT FIFTH WHEEL TRAILER, 2015 | JAYCO | PINNACLE FIFTH WHEEL TRAILER, 2015 | JAYCO | PRECEPT MOTORHOME, 2015 | JAYCO | REDHAWK MOTORHOME, 2015 | JAYCO | SEISMIC FIFTH WHEEL TRAILER, 2015 | JAYCO | SENECA CLASS C MOTORHOME, 2015 | JAYCO | WHITE HAWK TRAVEL TRAILER, 2016 | JAYCO | GREYHAWK MOTORHOME, 2016 | JAYCO | JAY FLIGHT TRAVEL TRAILER, 2016 | JAYCO | JAY SERIES, 2016 | JAYCO | REDHAWK MOTORHOME
Problème
Dans certains véhicules munis d'extincteurs Kidde à poignée et à robinet en plastique noir, les extincteurs pourraient se boucher ou nécessiter une force excessive pour être actionnés. De plus, la buse pourrait se séparer du robinet avec assez de force pour causer des blessures, et empêcher le fonctionnement de l'extincteur. En cas d'incendie, une défaillance de l'extincteur pourrait causer des blessures ou des dommages matériels (ou les deux). Mesure corrective : Les propriétaires recevront des instructions sur la manière d'inspecter l'extincteur afin de vérifier s'il fait l'objet d'un rappel. Des extincteurs de rechange seront fournis directement par Kidde. Remarque : Pour obtenir de plus amples renseignements sur les extincteurs faisant l'objet d'un rappel, veuillez consulter le site Web suivant : www.kidde.com.
Renseignements supplémentaires
Contexte
Vous pouvez trouver le rappel d’origine dans la Banque de données des rappels de sécurité automobile de Transports Canada.
Détails
Recevez des notifications
Recevez des courriels concernant les nouveaux rappels et avis de sécurité, ainsi que leurs mises à jour.