Rappel de véhicule

Numéro de rappel de Transports Canada - 2017635 - NEWMAR

Marque(s)
Dernière mise à jour

Résumé

Produit
Autocaravane rappelé par NEWMAR
Problème
Véhicules - Accessoires
Ce qu’il faut faire

Veuillez consulter la section des mesures correctives ci-dessous

Produits visés

1995 | NEWMAR | KOUNTRY AIRE CLASS A MOTORHOME, 1995 | NEWMAR | KOUNTRY STAR DIESEL PUSHER MOTORHOME, 1995 | NEWMAR | LONDON AIRE DIESEL PUSHER MOTORHOME, 1995 | NEWMAR | MOUNTAIN AIRE CLASS A MOTORHOME, 1995 | NEWMAR | MOUNTAIN AIRE DIESEL PUSHER MOTORHOME, 1996 | NEWMAR | KOUNTRY AIRE CLASS A MOTORHOME, 1996 | NEWMAR | KOUNTRY STAR DIESEL PUSHER MOTORHOME, 1996 | NEWMAR | LONDON AIRE DIESEL PUSHER MOTORHOME, 1996 | NEWMAR | MOUNTAIN AIRE CLASS A MOTORHOME, 1996 | NEWMAR | MOUNTAIN AIRE DIESEL PUSHER MOTORHOME, 1997 | NEWMAR | KOUNTRY AIRE CLASS A MOTORHOME, 1997 | NEWMAR | KOUNTRY AIRE DIESEL PUSHER MOTORHOME, 1997 | NEWMAR | LONDON AIRE DIESEL BUS, 1997 | NEWMAR | LONDON AIRE DIESEL PUSHER MOTORHOME, 1997 | NEWMAR | MOUNTAIN AIRE CLASS A MOTORHOME, 1997 | NEWMAR | MOUNTAIN AIRE DIESEL PUSHER MOTORHOME, 1998 | NEWMAR | DUTCH STAR CLASS A MOTORHOME, 1998 | NEWMAR | DUTCH STAR DIESEL PUSHER MOTORHOME, 1998 | NEWMAR | KOUNTRY AIRE CLASS A MOTORHOME, 1998 | NEWMAR | KOUNTRY STAR CLASS A MOTORHOME, 1998 | NEWMAR | LONDON AIRE DIESEL BUS, 1998 | NEWMAR | MOUNTAIN AIRE CLASS A MOTORHOME, 1998 | NEWMAR | MOUNTAIN AIRE DIESEL PUSHER MOTORHOME, 1999 | NEWMAR | DUTCH STAR CLASS A MOTORHOME, 1999 | NEWMAR | DUTCH STAR DIESEL PUSHER MOTORHOME, 1999 | NEWMAR | KOUNTRY STAR CLASS A MOTORHOME, 1999 | NEWMAR | LONDON AIRE DIESEL BUS, 1999 | NEWMAR | MOUNTAIN AIRE CLASS A MOTORHOME, 1999 | NEWMAR | MOUNTAIN AIRE DIESEL PUSHER MOTORHOME, 2000 | NEWMAR | DUTCH STAR CLASS A MOTORHOME, 2000 | NEWMAR | DUTCH STAR DIESEL PUSHER MOTORHOME, 2000 | NEWMAR | KOUNTRY STAR CLASS A MOTORHOME, 2000 | NEWMAR | KOUNTRY STAR DIESEL PUSHER MOTORHOME, 2000 | NEWMAR | LONDON AIRE DIESEL BUS, 2000 | NEWMAR | LONDON AIRE DIESEL PUSHER MOTORHOME, 2000 | NEWMAR | MOUNTAIN AIRE CLASS A MOTORHOME, 2000 | NEWMAR | MOUNTAIN AIRE DIESEL PUSHER MOTORHOME, 2001 | NEWMAR | DUTCH STAR CLASS A MOTORHOME, 2001 | NEWMAR | DUTCH STAR DIESEL PUSHER MOTORHOME, 2001 | NEWMAR | KOUNTRY AIRE DIESEL PUSHER MOTORHOME, 2001 | NEWMAR | KOUNTRY STAR CLASS A MOTORHOME, 2001 | NEWMAR | KOUNTRY STAR DIESEL PUSHER MOTORHOME, 2001 | NEWMAR | LONDON AIRE DIESEL BUS, 2001 | NEWMAR | MOUNTAIN AIRE CLASS A MOTORHOME, 2001 | NEWMAR | MOUNTAIN AIRE DIESEL PUSHER MOTORHOME, 2001 | NEWMAR | NEW AIRE CLASS A MOTORHOME, 2002 | NEWMAR | DUTCH STAR CLASS A MOTORHOME, 2002 | NEWMAR | DUTCH STAR DIESEL PUSHER MOTORHOME, 2002 | NEWMAR | KOUNTRY AIRE DIESEL PUSHER MOTORHOME, 2002 | NEWMAR | KOUNTRY STAR CLASS A MOTORHOME, 2002 | NEWMAR | KOUNTRY STAR DIESEL PUSHER MOTORHOME, 2002 | NEWMAR | LONDON AIRE DIESEL BUS, 2002 | NEWMAR | MOUNTAIN AIRE CLASS A MOTORHOME, 2002 | NEWMAR | MOUNTAIN AIRE DIESEL PUSHER MOTORHOME, 2002 | NEWMAR | MOUNTAIN AIRE LTD, 2002 | NEWMAR | NEW AIRE CLASS A MOTORHOME, 2002 | NEWMAR | NEW AIRE CLASSIC, 2003 | NEWMAR | DUTCH STAR DIESEL PUSHER MOTORHOME, 2003 | NEWMAR | ESSEX CLASS A MOTORHOME, 2003 | NEWMAR | KOUNTRY STAR CLASS A MOTORHOME, 2003 | NEWMAR | KOUNTRY STAR DIESEL PUSHER MOTORHOME, 2003 | NEWMAR | MOUNTAIN AIRE CLASS A MOTORHOME, 2003 | NEWMAR | MOUNTAIN AIRE DIESEL PUSHER MOTORHOME, 2003 | NEWMAR | NEW AIRE CLASS A MOTORHOME, 2003 | NEWMAR | SCOTTSDALE CLASS A MOTORHOME, 2004 | NEWMAR | DUTCH STAR DIESEL PUSHER MOTORHOME, 2004 | NEWMAR | ESSEX CLASS A MOTORHOME, 2004 | NEWMAR | KOUNTRY STAR CLASS A MOTORHOME, 2004 | NEWMAR | KOUNTRY STAR DIESEL PUSHER MOTORHOME, 2004 | NEWMAR | MOUNTAIN AIRE CLASS A MOTORHOME, 2004 | NEWMAR | MOUNTAIN AIRE DIESEL PUSHER MOTORHOME, 2004 | NEWMAR | NEW AIRE CLASS A MOTORHOME, 2004 | NEWMAR | NORTHERN STAR DIESEL PUSHER MOTORHOME, 2004 | NEWMAR | SCOTTSDALE CLASS A MOTORHOME, 2005 | NEWMAR | DUTCH STAR DIESEL PUSHER MOTORHOME, 2005 | NEWMAR | ESSEX CLASS A MOTORHOME, 2005 | NEWMAR | KOUNTRY STAR CLASS A MOTORHOME, 2005 | NEWMAR | KOUNTRY STAR DIESEL PUSHER MOTORHOME, 2005 | NEWMAR | MOUNTAIN AIRE CLASS A MOTORHOME, 2005 | NEWMAR | MOUNTAIN AIRE DIESEL PUSHER MOTORHOME, 2005 | NEWMAR | NEW AIRE CLASS A MOTORHOME, 2005 | NEWMAR | NORTHERN STAR DIESEL PUSHER MOTORHOME, 2005 | NEWMAR | SCOTTSDALE CLASS A MOTORHOME, 2006 | NEWMAR | DUTCH STAR DIESEL PUSHER MOTORHOME, 2006 | NEWMAR | ESSEX CLASS A MOTORHOME, 2006 | NEWMAR | KOUNTRY STAR CLASS A MOTORHOME, 2006 | NEWMAR | KOUNTRY STAR DIESEL PUSHER MOTORHOME, 2006 | NEWMAR | MOUNTAIN AIRE CLASS A MOTORHOME, 2006 | NEWMAR | MOUNTAIN AIRE DIESEL PUSHER MOTORHOME, 2006 | NEWMAR | NEW AIRE CLASS A MOTORHOME, 2006 | NEWMAR | SCOTTSDALE CLASS A MOTORHOME, 2006 | NEWMAR | VENTANA CLASS A MOTORHOME, 2007 | NEWMAR | ALL STAR DIESEL PUSHER MOTORHOME, 2007 | NEWMAR | BAY STAR, 2007 | NEWMAR | BAY STAR CLASS A MOTORHOME, 2007 | NEWMAR | CANYON STAR CLASS A MOTORHOME, 2007 | NEWMAR | DUTCH STAR DIESEL PUSHER MOTORHOME, 2007 | NEWMAR | ESSEX CLASS A MOTORHOME, 2007 | NEWMAR | KOUNTRY STAR CLASS A MOTORHOME, 2007 | NEWMAR | KOUNTRY STAR DIESEL PUSHER MOTORHOME, 2007 | NEWMAR | MOUNTAIN AIRE CLASS A MOTORHOME, 2007 | NEWMAR | MOUNTAIN AIRE DIESEL PUSHER MOTORHOME, 2007 | NEWMAR | NEW AIRE CLASS A MOTORHOME, 2007 | NEWMAR | VENTANA CLASS A MOTORHOME, 2008 | NEWMAR | ALL STAR DIESEL PUSHER MOTORHOME, 2008 | NEWMAR | BAY STAR, 2008 | NEWMAR | BAY STAR CLASS A MOTORHOME, 2008 | NEWMAR | CANYON STAR CLASS A MOTORHOME, 2008 | NEWMAR | DUTCH STAR DIESEL PUSHER MOTORHOME, 2008 | NEWMAR | ESSEX CLASS A MOTORHOME, 2008 | NEWMAR | GRAND STAR CLASS A MOTORHOME, 2008 | NEWMAR | KING AIRE CLASS A MOTORHOME, 2008 | NEWMAR | KING AIRE MOTORHOME, 2008 | NEWMAR | KOUNTRY STAR DIESEL PUSHER MOTORHOME, 2008 | NEWMAR | MOUNTAIN AIRE DIESEL PUSHER MOTORHOME, 2008 | NEWMAR | NEW AIRE CLASS A MOTORHOME, 2008 | NEWMAR | VENTANA CLASS A MOTORHOME, 2009 | NEWMAR | BAY STAR, 2009 | NEWMAR | BAY STAR CLASS A MOTORHOME, 2009 | NEWMAR | CANYON STAR CLASS A MOTORHOME, 2009 | NEWMAR | DUTCH AIRE DIESEL PUSHER MOTORHOME, 2009 | NEWMAR | DUTCH STAR DIESEL PUSHER MOTORHOME, 2009 | NEWMAR | ESSEX CLASS A MOTORHOME, 2009 | NEWMAR | GRAND STAR CLASS A MOTORHOME, 2009 | NEWMAR | KING AIRE CLASS A MOTORHOME, 2009 | NEWMAR | KING AIRE MOTORHOME, 2009 | NEWMAR | MOUNTAIN AIRE DIESEL PUSHER MOTORHOME, 2009 | NEWMAR | NEW AIRE CLASS A MOTORHOME, 2009 | NEWMAR | VENTANA CLASS A MOTORHOME, 2010 | NEWMAR | BAY STAR, 2010 | NEWMAR | BAY STAR CLASS A MOTORHOME, 2010 | NEWMAR | CANYON STAR CLASS A MOTORHOME, 2010 | NEWMAR | DUTCH AIRE DIESEL PUSHER MOTORHOME, 2010 | NEWMAR | DUTCH STAR DIESEL PUSHER MOTORHOME, 2010 | NEWMAR | ESSEX CLASS A MOTORHOME, 2010 | NEWMAR | KING AIRE CLASS A MOTORHOME, 2010 | NEWMAR | KING AIRE MOTORHOME, 2010 | NEWMAR | NEW AIRE CLASS A MOTORHOME, 2010 | NEWMAR | VENTANA CLASS A MOTORHOME, 2011 | NEWMAR | BAY STAR, 2011 | NEWMAR | BAY STAR CLASS A MOTORHOME, 2011 | NEWMAR | CANYON STAR CLASS A MOTORHOME, 2011 | NEWMAR | DUTCH STAR DIESEL PUSHER MOTORHOME, 2011 | NEWMAR | ESSEX CLASS A MOTORHOME, 2011 | NEWMAR | KING AIRE CLASS A MOTORHOME, 2011 | NEWMAR | KING AIRE MOTORHOME, 2011 | NEWMAR | MOUNTAIN AIRE DIESEL PUSHER MOTORHOME, 2011 | NEWMAR | NEW AIRE CLASS A MOTORHOME, 2011 | NEWMAR | VENTANA CLASS A MOTORHOME, 2012 | NEWMAR | BAY STAR, 2012 | NEWMAR | BAY STAR CLASS A MOTORHOME, 2012 | NEWMAR | BAY STAR SPORT CLASS A MOTORHOME, 2012 | NEWMAR | CANYON STAR CLASS A MOTORHOME, 2012 | NEWMAR | DUTCH STAR DIESEL PUSHER MOTORHOME, 2012 | NEWMAR | ESSEX CLASS A MOTORHOME, 2012 | NEWMAR | KING AIRE CLASS A MOTORHOME, 2012 | NEWMAR | KING AIRE MOTORHOME, 2012 | NEWMAR | MOUNTAIN AIRE DIESEL PUSHER MOTORHOME, 2012 | NEWMAR | NEW AIRE CLASS A MOTORHOME, 2012 | NEWMAR | VENTANA CLASS A MOTORHOME, 2012 | NEWMAR | VENTANA LE CLASS A MOTORHOME, 2013 | NEWMAR | BAY STAR, 2013 | NEWMAR | BAY STAR CLASS A MOTORHOME, 2013 | NEWMAR | BAY STAR SPORT CLASS A MOTORHOME, 2013 | NEWMAR | CANYON STAR CLASS A MOTORHOME, 2013 | NEWMAR | DUTCH STAR DIESEL PUSHER MOTORHOME, 2013 | NEWMAR | ESSEX CLASS A MOTORHOME, 2013 | NEWMAR | KING AIRE CLASS A MOTORHOME, 2013 | NEWMAR | KING AIRE MOTORHOME, 2013 | NEWMAR | MOUNTAIN AIRE DIESEL PUSHER MOTORHOME, 2013 | NEWMAR | NEW AIRE CLASS A MOTORHOME, 2013 | NEWMAR | VENTANA CLASS A MOTORHOME, 2013 | NEWMAR | VENTANA LE CLASS A MOTORHOME, 2014 | NEWMAR | BAY STAR, 2014 | NEWMAR | BAY STAR CLASS A MOTORHOME, 2014 | NEWMAR | BAY STAR SPORT CLASS A MOTORHOME, 2014 | NEWMAR | CANYON STAR CLASS A MOTORHOME, 2014 | NEWMAR | DUTCH STAR DIESEL PUSHER MOTORHOME, 2014 | NEWMAR | ESSEX CLASS A MOTORHOME, 2014 | NEWMAR | KING AIRE CLASS A MOTORHOME, 2014 | NEWMAR | KING AIRE MOTORHOME, 2014 | NEWMAR | MOUNTAIN AIRE DIESEL PUSHER MOTORHOME, 2014 | NEWMAR | NEW AIRE CLASS A MOTORHOME, 2014 | NEWMAR | VENTANA CLASS A MOTORHOME, 2014 | NEWMAR | VENTANA LE CLASS A MOTORHOME, 2015 | NEWMAR | BAY STAR, 2015 | NEWMAR | BAY STAR CLASS A MOTORHOME, 2015 | NEWMAR | BAY STAR SPORT CLASS A MOTORHOME, 2015 | NEWMAR | CANYON STAR CLASS A MOTORHOME, 2015 | NEWMAR | DUTCH STAR DIESEL PUSHER MOTORHOME, 2015 | NEWMAR | ESSEX CLASS A MOTORHOME, 2015 | NEWMAR | KING AIRE CLASS A MOTORHOME, 2015 | NEWMAR | KING AIRE MOTORHOME, 2015 | NEWMAR | LONDON AIRE DIESEL PUSHER MOTORHOME, 2015 | NEWMAR | MOUNTAIN AIRE DIESEL PUSHER MOTORHOME, 2015 | NEWMAR | NEW AIRE CLASS A MOTORHOME, 2015 | NEWMAR | VENTANA CLASS A MOTORHOME, 2015 | NEWMAR | VENTANA LE CLASS A MOTORHOME, 2016 | NEWMAR | BAY STAR, 2016 | NEWMAR | BAY STAR CLASS A MOTORHOME, 2016 | NEWMAR | BAY STAR SPORT CLASS A MOTORHOME, 2016 | NEWMAR | CANYON STAR CLASS A MOTORHOME, 2016 | NEWMAR | DUTCH STAR DIESEL PUSHER MOTORHOME, 2016 | NEWMAR | ESSEX CLASS A MOTORHOME, 2016 | NEWMAR | KING AIRE CLASS A MOTORHOME, 2016 | NEWMAR | KING AIRE MOTORHOME, 2016 | NEWMAR | LONDON AIRE DIESEL PUSHER MOTORHOME, 2016 | NEWMAR | MOUNTAIN AIRE DIESEL PUSHER MOTORHOME, 2016 | NEWMAR | NEW AIRE CLASS A MOTORHOME, 2016 | NEWMAR | VENTANA CLASS A MOTORHOME, 2016 | NEWMAR | VENTANA LE CLASS A MOTORHOME, 2017 | NEWMAR | BAY STAR, 2017 | NEWMAR | BAY STAR CLASS A MOTORHOME, 2017 | NEWMAR | BAY STAR SPORT CLASS A MOTORHOME, 2017 | NEWMAR | CANYON STAR CLASS A MOTORHOME, 2017 | NEWMAR | DUTCH STAR DIESEL PUSHER MOTORHOME, 2017 | NEWMAR | ESSEX CLASS A MOTORHOME, 2017 | NEWMAR | KING AIRE CLASS A MOTORHOME, 2017 | NEWMAR | KING AIRE MOTORHOME, 2017 | NEWMAR | LONDON AIRE DIESEL PUSHER MOTORHOME, 2017 | NEWMAR | MOUNTAIN AIRE DIESEL PUSHER MOTORHOME, 2017 | NEWMAR | NEW AIRE CLASS A MOTORHOME, 2017 | NEWMAR | VENTANA CLASS A MOTORHOME, 2017 | NEWMAR | VENTANA LE CLASS A MOTORHOME, 2018 | NEWMAR | BAY STAR, 2018 | NEWMAR | BAY STAR CLASS A MOTORHOME, 2018 | NEWMAR | BAY STAR SPORT CLASS A MOTORHOME, 2018 | NEWMAR | CANYON STAR CLASS A MOTORHOME, 2018 | NEWMAR | DUTCH STAR DIESEL PUSHER MOTORHOME, 2018 | NEWMAR | ESSEX CLASS A MOTORHOME, 2018 | NEWMAR | KING AIRE CLASS A MOTORHOME, 2018 | NEWMAR | KING AIRE MOTORHOME, 2018 | NEWMAR | LONDON AIRE DIESEL PUSHER MOTORHOME, 2018 | NEWMAR | MOUNTAIN AIRE DIESEL PUSHER MOTORHOME, 2018 | NEWMAR | NEW AIRE CLASS A MOTORHOME, 2018 | NEWMAR | VENTANA CLASS A MOTORHOME, 2018 | NEWMAR | VENTANA LE CLASS A MOTORHOME

Problème

Dans certains véhicules munis d'extincteurs Kidde à poignée et à robinet en plastique noir, les extincteurs pourraient se boucher ou nécessiter une force excessive pour être actionnés. De plus, la buse pourrait se séparer du robinet avec assez de force pour causer des blessures, et empêcher le fonctionnement de l'extincteur. En cas d'incendie, une défaillance de l'extincteur pourrait causer des blessures ou des dommages matériels (ou les deux). Mesure corrective : Les propriétaires recevront des instructions sur la manière d'inspecter l'extincteur afin de vérifier s'il fait l'objet d'un rappel. Des extincteurs de rechange seront fournis directement par Kidde. Remarque : Pour obtenir de plus amples renseignements sur les extincteurs faisant l'objet d'un rappel, veuillez consulter le site Web suivant : www.kidde.com.

Renseignements supplémentaires

Contexte

Vous pouvez trouver le rappel d’origine dans la Banque de données des rappels de sécurité automobile de Transports Canada.

Détails
Date de publication originale :
Type d’avis ou de rappel
Rappel de véhicule
Catégorie
Véhicules - Autocaravane
Entreprises
Publié par
Transports Canada
Auditoire
Grand public
Numéro d’identification
RA-67853
Transports Canada Identifiant (ID)
2017635