Numéro de rappel de Transports Canada - 2017613 - THOR MOTOR COACH
Marque(s)
Résumé
Veuillez consulter la section des mesures correctives ci-dessous
Produits visés
2003 | THOR MOTOR COACH | CHALLENGER, 2003 | THOR MOTOR COACH | CHATEAU, 2003 | THOR MOTOR COACH | DUTCHMEN, 2003 | THOR MOTOR COACH | ESCAPER, 2003 | THOR MOTOR COACH | FOUR WINDS, 2003 | THOR MOTOR COACH | FUN MOVER, 2003 | THOR MOTOR COACH | HURRICANE, 2003 | THOR MOTOR COACH | INFINITY, 2003 | THOR MOTOR COACH | MAJESTIC, 2003 | THOR MOTOR COACH | MANDALAY, 2003 | THOR MOTOR COACH | ULTRASPORT, 2003 | THOR MOTOR COACH | WINDSPORT, 2004 | THOR MOTOR COACH | CHALLENGER, 2004 | THOR MOTOR COACH | CHATEAU, 2004 | THOR MOTOR COACH | CHATEAU CITATION, 2004 | THOR MOTOR COACH | DAYBREAK, 2004 | THOR MOTOR COACH | DUTCHMEN, 2004 | THOR MOTOR COACH | DUTCHMEN DORADO, 2004 | THOR MOTOR COACH | ESCAPER, 2004 | THOR MOTOR COACH | FOUR WINDS, 2004 | THOR MOTOR COACH | FOUR WINDS SIESTA, 2004 | THOR MOTOR COACH | FUN MOVER, 2004 | THOR MOTOR COACH | HURRICANE, 2004 | THOR MOTOR COACH | INFINITY, 2004 | THOR MOTOR COACH | MAJESTIC, 2004 | THOR MOTOR COACH | MANDALAY, 2004 | THOR MOTOR COACH | PRESIDIO, 2004 | THOR MOTOR COACH | ULTRASPORT, 2004 | THOR MOTOR COACH | WINDSPORT, 2005 | THOR MOTOR COACH | ASTORIA, 2005 | THOR MOTOR COACH | CHALLENGER, 2005 | THOR MOTOR COACH | CHATEAU, 2005 | THOR MOTOR COACH | CHATEAU CITATION, 2005 | THOR MOTOR COACH | DAYBREAK, 2005 | THOR MOTOR COACH | DUTCHMEN, 2005 | THOR MOTOR COACH | DUTCHMEN DORADO, 2005 | THOR MOTOR COACH | ESCAPER, 2005 | THOR MOTOR COACH | FOUR WINDS, 2005 | THOR MOTOR COACH | FOUR WINDS SIESTA, 2005 | THOR MOTOR COACH | FUN MOVER, 2005 | THOR MOTOR COACH | HURRICANE, 2005 | THOR MOTOR COACH | INFINITY, 2005 | THOR MOTOR COACH | MAJESTIC, 2005 | THOR MOTOR COACH | MANDALAY, 2005 | THOR MOTOR COACH | PRESIDIO, 2005 | THOR MOTOR COACH | TUSCANY, 2005 | THOR MOTOR COACH | ULTRASPORT, 2005 | THOR MOTOR COACH | WINDSPORT, 2006 | THOR MOTOR COACH | ASTORIA, 2006 | THOR MOTOR COACH | CHALLENGER, 2006 | THOR MOTOR COACH | CHATEAU, 2006 | THOR MOTOR COACH | CHATEAU CITATION, 2006 | THOR MOTOR COACH | DAYBREAK, 2006 | THOR MOTOR COACH | DUTCHMEN, 2006 | THOR MOTOR COACH | DUTCHMEN DORADO, 2006 | THOR MOTOR COACH | FOUR WINDS, 2006 | THOR MOTOR COACH | FOUR WINDS SIESTA, 2006 | THOR MOTOR COACH | FUN MOVER, 2006 | THOR MOTOR COACH | HURRICANE, 2006 | THOR MOTOR COACH | INFINITY, 2006 | THOR MOTOR COACH | MAGELLAN, 2006 | THOR MOTOR COACH | MAJESTIC, 2006 | THOR MOTOR COACH | MANDALAY, 2006 | THOR MOTOR COACH | PRESIDIO, 2006 | THOR MOTOR COACH | TUSCANY, 2006 | THOR MOTOR COACH | VALENCIA, 2006 | THOR MOTOR COACH | WINDSPORT, 2007 | THOR MOTOR COACH | ASTORIA, 2007 | THOR MOTOR COACH | ASTORIA PACIFIC, 2007 | THOR MOTOR COACH | CHALLENGER, 2007 | THOR MOTOR COACH | CHATEAU, 2007 | THOR MOTOR COACH | CHATEAU CITATION, 2007 | THOR MOTOR COACH | CRUISE TRAVEL TRAILER, 2007 | THOR MOTOR COACH | DAYBREAK, 2007 | THOR MOTOR COACH | DUTCHMEN, 2007 | THOR MOTOR COACH | DUTCHMEN DORADO, 2007 | THOR MOTOR COACH | FOUR WINDS, 2007 | THOR MOTOR COACH | FOUR WINDS SIESTA, 2007 | THOR MOTOR COACH | FUN MOVER, 2007 | THOR MOTOR COACH | HURRICANE, 2007 | THOR MOTOR COACH | MAGELLAN, 2007 | THOR MOTOR COACH | MAJESTIC, 2007 | THOR MOTOR COACH | MAJESTIC FLYER, 2007 | THOR MOTOR COACH | MAJESTIC TRAVEL TRAILER, 2007 | THOR MOTOR COACH | MANDALAY, 2007 | THOR MOTOR COACH | OUTLAW, 2007 | THOR MOTOR COACH | PRESIDIO, 2007 | THOR MOTOR COACH | TUSCANY, 2007 | THOR MOTOR COACH | VALENCIA, 2007 | THOR MOTOR COACH | WINDSPORT, 2008 | THOR MOTOR COACH | ASTORIA, 2008 | THOR MOTOR COACH | ASTORIA PACIFIC, 2008 | THOR MOTOR COACH | CHALLENGER, 2008 | THOR MOTOR COACH | CHALLENGER PLATINUM, 2008 | THOR MOTOR COACH | CHATEAU, 2008 | THOR MOTOR COACH | CHATEAU CITATION, 2008 | THOR MOTOR COACH | DAYBREAK, 2008 | THOR MOTOR COACH | DUTCHMEN, 2008 | THOR MOTOR COACH | DUTCHMEN DORADO, 2008 | THOR MOTOR COACH | ESSENCE, 2008 | THOR MOTOR COACH | FOUR WINDS, 2008 | THOR MOTOR COACH | FOUR WINDS SIESTA, 2008 | THOR MOTOR COACH | FUN MOVER, 2008 | THOR MOTOR COACH | HURRICANE, 2008 | THOR MOTOR COACH | MAGELLAN, 2008 | THOR MOTOR COACH | MAJESTIC, 2008 | THOR MOTOR COACH | MANDALAY, 2008 | THOR MOTOR COACH | OUTLAW, 2008 | THOR MOTOR COACH | PRESEDIO 360, 2008 | THOR MOTOR COACH | PRESIDIO, 2008 | THOR MOTOR COACH | TUSCANY, 2008 | THOR MOTOR COACH | WINDSPORT, 2009 | THOR MOTOR COACH | ASTORIA, 2009 | THOR MOTOR COACH | ASTORIA PACIFIC, 2009 | THOR MOTOR COACH | AVANTI, 2009 | THOR MOTOR COACH | CHALLENGER, 2009 | THOR MOTOR COACH | CHALLENGER PLATINUM, 2009 | THOR MOTOR COACH | CHATEAU, 2009 | THOR MOTOR COACH | CHATEAU CITATION, 2009 | THOR MOTOR COACH | DAYBREAK, 2009 | THOR MOTOR COACH | DAYBREAK SPORT, 2009 | THOR MOTOR COACH | DEL RAY, 2009 | THOR MOTOR COACH | DUTCHMEN, 2009 | THOR MOTOR COACH | DUTCHMEN DORADO, 2009 | THOR MOTOR COACH | ESSENCE, 2009 | THOR MOTOR COACH | FOUR WINDS, 2009 | THOR MOTOR COACH | FOUR WINDS SIESTA, 2009 | THOR MOTOR COACH | FUN MOVER, 2009 | THOR MOTOR COACH | HURRICANE, 2009 | THOR MOTOR COACH | MAGELLAN, 2009 | THOR MOTOR COACH | MAJESTIC, 2009 | THOR MOTOR COACH | MANDALAY, 2009 | THOR MOTOR COACH | OUTLAW, 2009 | THOR MOTOR COACH | PRESEDIO 360, 2009 | THOR MOTOR COACH | PRESIDIO, 2009 | THOR MOTOR COACH | SERRANO, 2009 | THOR MOTOR COACH | TUSCANY, 2009 | THOR MOTOR COACH | VENTURA, 2009 | THOR MOTOR COACH | WINDSPORT, 2010 | FOUR WINDS | MONTECITO, 2010 | THOR MOTOR COACH | ASTORIA, 2010 | THOR MOTOR COACH | AVANTI, 2010 | THOR MOTOR COACH | CHALLENGER, 2010 | THOR MOTOR COACH | CHALLENGER PLATINUM, 2010 | THOR MOTOR COACH | CHATEAU, 2010 | THOR MOTOR COACH | CHATEAU CITATION, 2010 | THOR MOTOR COACH | DAYBREAK, 2010 | THOR MOTOR COACH | DAYBREAK CLASSIC SPORT, 2010 | THOR MOTOR COACH | DAYBREAK SPORT, 2010 | THOR MOTOR COACH | DUTCHMEN, 2010 | THOR MOTOR COACH | DUTCHMEN DORADO, 2010 | THOR MOTOR COACH | ESSENCE, 2010 | THOR MOTOR COACH | FOUR WINDS, 2010 | THOR MOTOR COACH | FOUR WINDS SIESTA, 2010 | THOR MOTOR COACH | FREEDOM ELITE, 2010 | THOR MOTOR COACH | FUN MOVER, 2010 | THOR MOTOR COACH | HURRICANE, 2010 | THOR MOTOR COACH | MAGELLAN, 2010 | THOR MOTOR COACH | MAJESTIC, 2010 | THOR MOTOR COACH | MANDALAY, 2010 | THOR MOTOR COACH | OUTLAW, 2010 | THOR MOTOR COACH | SERRANO, 2010 | THOR MOTOR COACH | TUSCANY, 2010 | THOR MOTOR COACH | VENTURA, 2010 | THOR MOTOR COACH | WINDSPORT, 2011 | FOUR WINDS | MONTECITO, 2011 | THOR MOTOR COACH | ACE, 2011 | THOR MOTOR COACH | ASTORIA, 2011 | THOR MOTOR COACH | AVANTI, 2011 | THOR MOTOR COACH | CHALLENGER, 2011 | THOR MOTOR COACH | CHATEAU, 2011 | THOR MOTOR COACH | CHATEAU CITATION, 2011 | THOR MOTOR COACH | DAYBREAK, 2011 | THOR MOTOR COACH | FOUR WINDS, 2011 | THOR MOTOR COACH | FOUR WINDS SIESTA, 2011 | THOR MOTOR COACH | FREEDOM ELITE, 2011 | THOR MOTOR COACH | HURRICANE, 2011 | THOR MOTOR COACH | MAJESTIC, 2011 | THOR MOTOR COACH | OUTLAW, 2011 | THOR MOTOR COACH | SERRANO, 2011 | THOR MOTOR COACH | TUSCANY, 2011 | THOR MOTOR COACH | WINDSPORT, 2012 | THOR MOTOR COACH | ACE, 2012 | THOR MOTOR COACH | ASTORIA, 2012 | THOR MOTOR COACH | AVANTI, 2012 | THOR MOTOR COACH | CHALLENGER, 2012 | THOR MOTOR COACH | CHATEAU, 2012 | THOR MOTOR COACH | CHATEAU CITATION, 2012 | THOR MOTOR COACH | DAYBREAK, 2012 | THOR MOTOR COACH | FOUR WINDS, 2012 | THOR MOTOR COACH | FOUR WINDS SIESTA, 2012 | THOR MOTOR COACH | FREEDOM ELITE, 2012 | THOR MOTOR COACH | HURRICANE, 2012 | THOR MOTOR COACH | MAJESTIC, 2012 | THOR MOTOR COACH | OUTLAW, 2012 | THOR MOTOR COACH | SERRANO, 2012 | THOR MOTOR COACH | TUSCANY, 2012 | THOR MOTOR COACH | WINDSPORT, 2013 | THOR MOTOR COACH | ACE, 2013 | THOR MOTOR COACH | CHALLENGER, 2013 | THOR MOTOR COACH | CHATEAU, 2013 | THOR MOTOR COACH | CHATEAU CITATION, 2013 | THOR MOTOR COACH | DAYBREAK, 2013 | THOR MOTOR COACH | FOUR WINDS, 2013 | THOR MOTOR COACH | FOUR WINDS SIESTA, 2013 | THOR MOTOR COACH | FREEDOM ELITE, 2013 | THOR MOTOR COACH | HURRICANE, 2013 | THOR MOTOR COACH | MAJESTIC, 2013 | THOR MOTOR COACH | OUTLAW, 2013 | THOR MOTOR COACH | PALAZZO, 2013 | THOR MOTOR COACH | SERRANO, 2013 | THOR MOTOR COACH | TUSCANY, 2013 | THOR MOTOR COACH | WINDSPORT, 2014 | THOR MOTOR COACH | ACE, 2014 | THOR MOTOR COACH | AXIS, 2014 | THOR MOTOR COACH | CHALLENGER, 2014 | THOR MOTOR COACH | CHATEAU, 2014 | THOR MOTOR COACH | CHATEAU CITATION, 2014 | THOR MOTOR COACH | DAYBREAK, 2014 | THOR MOTOR COACH | FOUR WINDS, 2014 | THOR MOTOR COACH | FOUR WINDS SIESTA, 2014 | THOR MOTOR COACH | FREEDOM ELITE, 2014 | THOR MOTOR COACH | HURRICANE, 2014 | THOR MOTOR COACH | MAJESTIC, 2014 | THOR MOTOR COACH | MIRAMAR, 2014 | THOR MOTOR COACH | OUTLAW, 2014 | THOR MOTOR COACH | OUTLAW C, 2014 | THOR MOTOR COACH | PALAZZO, 2014 | THOR MOTOR COACH | TUSCANY, 2014 | THOR MOTOR COACH | TUSCANY XTE, 2014 | THOR MOTOR COACH | VEGAS, 2014 | THOR MOTOR COACH | WINDSPORT, 2015 | THOR MOTOR COACH | ACE, 2015 | THOR MOTOR COACH | AXIS, 2015 | THOR MOTOR COACH | CHALLENGER, 2015 | THOR MOTOR COACH | CHATEAU, 2015 | THOR MOTOR COACH | CHATEAU CITATION, 2015 | THOR MOTOR COACH | FOUR WINDS, 2015 | THOR MOTOR COACH | FOUR WINDS SIESTA, 2015 | THOR MOTOR COACH | FREEDOM ELITE, 2015 | THOR MOTOR COACH | HURRICANE, 2015 | THOR MOTOR COACH | MAJESTIC, 2015 | THOR MOTOR COACH | MIRAMAR, 2015 | THOR MOTOR COACH | OUTLAW, 2015 | THOR MOTOR COACH | OUTLAW C, 2015 | THOR MOTOR COACH | PALAZZO, 2015 | THOR MOTOR COACH | TUSCANY, 2015 | THOR MOTOR COACH | TUSCANY XTE, 2015 | THOR MOTOR COACH | VEGAS, 2015 | THOR MOTOR COACH | WINDSPORT, 2016 | THOR MOTOR COACH | ACE, 2016 | THOR MOTOR COACH | AXIS, 2016 | THOR MOTOR COACH | CHALLENGER, 2016 | THOR MOTOR COACH | CHATEAU, 2016 | THOR MOTOR COACH | CHATEAU CITATION, 2016 | THOR MOTOR COACH | FOUR WINDS, 2016 | THOR MOTOR COACH | FOUR WINDS SIESTA, 2016 | THOR MOTOR COACH | FREEDOM ELITE, 2016 | THOR MOTOR COACH | GEMINI, 2016 | THOR MOTOR COACH | HURRICANE, 2016 | THOR MOTOR COACH | MAJESTIC, 2016 | THOR MOTOR COACH | MIRAMAR, 2016 | THOR MOTOR COACH | OUTLAW, 2016 | THOR MOTOR COACH | OUTLAW C, 2016 | THOR MOTOR COACH | PALAZZO, 2016 | THOR MOTOR COACH | QUANTUM, 2016 | THOR MOTOR COACH | SYNERGY, 2016 | THOR MOTOR COACH | TUSCANY, 2016 | THOR MOTOR COACH | TUSCANY XTE, 2016 | THOR MOTOR COACH | VEGAS, 2016 | THOR MOTOR COACH | VENETIAN, 2016 | THOR MOTOR COACH | WINDSPORT, 2017 | THOR MOTOR COACH | ACE, 2017 | THOR MOTOR COACH | ARIA, 2017 | THOR MOTOR COACH | AXIS, 2017 | THOR MOTOR COACH | CHALLENGER, 2017 | THOR MOTOR COACH | CHATEAU, 2017 | THOR MOTOR COACH | CHATEAU CITATION, 2017 | THOR MOTOR COACH | EL MONTE CLASS A, 2017 | THOR MOTOR COACH | FOUR WINDS, 2017 | THOR MOTOR COACH | FOUR WINDS SIESTA, 2017 | THOR MOTOR COACH | FREEDOM ELITE, 2017 | THOR MOTOR COACH | GEMINI, 2017 | THOR MOTOR COACH | HURRICANE, 2017 | THOR MOTOR COACH | MAJESTIC, 2017 | THOR MOTOR COACH | MIRAMAR, 2017 | THOR MOTOR COACH | OUTLAW, 2017 | THOR MOTOR COACH | OUTLAW C, 2017 | THOR MOTOR COACH | PALAZZO, 2017 | THOR MOTOR COACH | QUANTUM, 2017 | THOR MOTOR COACH | SYNERGY, 2017 | THOR MOTOR COACH | TUSCANY, 2017 | THOR MOTOR COACH | TUSCANY XTE, 2017 | THOR MOTOR COACH | VEGAS, 2017 | THOR MOTOR COACH | VENETIAN, 2017 | THOR MOTOR COACH | WINDSPORT, 2018 | THOR MOTOR COACH | ACE, 2018 | THOR MOTOR COACH | ARIA, 2018 | THOR MOTOR COACH | AXIS, 2018 | THOR MOTOR COACH | CHALLENGER, 2018 | THOR MOTOR COACH | CHATEAU, 2018 | THOR MOTOR COACH | CHATEAU CITATION, 2018 | THOR MOTOR COACH | EL MONTE CLASS A, 2018 | THOR MOTOR COACH | FOUR WINDS, 2018 | THOR MOTOR COACH | FOUR WINDS SIESTA, 2018 | THOR MOTOR COACH | FREEDOM ELITE, 2018 | THOR MOTOR COACH | GEMINI, 2018 | THOR MOTOR COACH | HURRICANE, 2018 | THOR MOTOR COACH | MAJESTIC, 2018 | THOR MOTOR COACH | MIRAMAR, 2018 | THOR MOTOR COACH | OUTLAW, 2018 | THOR MOTOR COACH | OUTLAW C, 2018 | THOR MOTOR COACH | PALAZZO, 2018 | THOR MOTOR COACH | QUANTUM, 2018 | THOR MOTOR COACH | SYNERGY, 2018 | THOR MOTOR COACH | TUSCANY, 2018 | THOR MOTOR COACH | VEGAS, 2018 | THOR MOTOR COACH | VENETIAN, 2018 | THOR MOTOR COACH | WINDSPORT
Problème
Dans certains véhicules munis d'extincteurs Kidde à poignée et à robinet en plastique noir, les extincteurs pourraient se boucher ou nécessiter une force excessive pour être actionnés. De plus, la buse pourrait se séparer du robinet avec assez de force pour causer des blessures, et empêcher le fonctionnement de l'extincteur. En cas d'incendie, une défaillance de l'extincteur pourrait causer des blessures ou des dommages matériels (ou les deux). Mesure corrective : Les propriétaires recevront des instructions sur la manière d'inspecter l'extincteur afin de vérifier s'il fait l'objet d'un rappel. Des extincteurs de rechange seront fournis directement par Kidde. Remarque : Pour obtenir de plus amples renseignements sur les extincteurs faisant l'objet d'un rappel, veuillez consulter le site Web suivant : www.kidde.com.
Renseignements supplémentaires
Contexte
Vous pouvez trouver le rappel d’origine dans la Banque de données des rappels de sécurité automobile de Transports Canada.
Détails
Recevez des notifications
Recevez des courriels concernant les nouveaux rappels et avis de sécurité, ainsi que leurs mises à jour.