Transport Canada Recall - 2023424 - ALTEC INDUSTRIES
Brand(s)
Summary
Please see corrective actions section below
Affected products
2022 | ALTEC | LR8 SERIES, 2022 | ALTEC | AM SERIES, 2022 | ALTEC | DH SERIES, 2022 | ALTEC | AT SERIES, 2022 | ALTEC | L45, 2022 | ALTEC | D SERIES, 2022 | ALTEC | DM SERIES, 2022 | ALTEC | TA SERIES, 2022 | ALTEC | AN SERIES, 2022 | ALTEC | AA SERIES, 2022 | ALTEC | DL, 2023 | ALTEC | TA SERIES, 2023 | ALTEC | AA SERIES, 2023 | ALTEC | LR8 SERIES, 2023 | ALTEC | AM SERIES, 2023 | ALTEC | DH SERIES, 2023 | ALTEC | DM SERIES, 2023 | ALTEC | D SERIES, 2023 | ALTEC | L45, 2023 | ALTEC | AN SERIES, 2023 | ALTEC | DL, 2023 | ALTEC | AT SERIES
Issue
On certain aerial devices and digger derricks, the inverter module may not have proper circuit protection for the AC output. As a result, the wiring could overheat and melt.
Safety risk
Wiring that doesn't have proper circuit protection could create a fire risk.
Corrective actions
Altec Industries will notify owners by mail and advise you to contact Altec Service to install a 20 A circuit breaker for the inverter AC output. Altec advises not to use the inverter AC output until the recall repairs are completed.